Preliminary assessment of fire damaged reinforced concrete structure and steel truss
Khiyon, M. Iqbal1, Mariyana Aida Ab. Kadir2, Siti Nurul Nureda Mohamad Zukri3, Mohd Hanim Osman4.
The assessment of fire damaged structure is an area which considered new and have
little practical experience in Malaysia. In this study the objective are to determine the concrete
strength and the ultimate strength of steel truss and weight loss of the steel after exposure to fire.
Non-destructive and destructive test has been tested in this study. Rebound hammer test had been
done to determine the strength of the concrete beam while tensile test and corrosion test both
have been done by taking samples from the steel purlin. The test conducted in this study follows
the BS EN 10 002: Part 1: 1990, ISO 6892-1 and ASTM G1-90. The results from rebound
hammer test, the compressive strength of the concrete beam is between 40 ± 4 N/mm² while the
average ultimate strength of steel truss is between 412 N/mm² to 434 N/mm². Meanwhile, for the
corrosion test, when steel 0.17%. This testing shows that steel has loss, its mechanical properties due to exposed to elevated temperature. By conducting a non-destructive test for concrete and destructive test for steel it shows to be practical and useful in evaluating the fire damaged reinforced concrete structure and steel truss.
Affiliation:
- Universiti Teknologi Malaysia, Malaysia
- Universiti Teknologi Malaysia, Malaysia
- Universiti Teknologi Malaysia, Malaysia
- Universiti Teknologi Malaysia, Malaysia
Download this article (This article has been downloaded 210 time(s))
|
|
Indexation |
Indexed by |
MyJurnal (2021) |
H-Index
|
3 |
Immediacy Index
|
0.000 |
Rank |
0 |
|
|
|