Energy analysis for lighting and airconditioning system of an academic building
Tee, Boon Tuan1, Ahmad Zubair Yahaya2, Younus Fahad Breesam3, Reduan Mat Dan4, Muhammad Zulfattah Zakaria5.
Energy analysis is important to analyze energy consumption pattern, monitoring on
how the energy used varies with time in the building and how the system element
interrelate. In this case study, a preliminary energy audit is done on lighting and airconditioning
system. The lighting and airconditioning system consume the highest
amount from the total building energy usage. The study was conducted in the
Faculty of Mechanical Engineering Building, Universiti Teknikal Malaysia (UTeM)
Technology Campus. From the result shows that the air-conditioning system has
contributed approximately 48.8% from the total monthly energy usage. The
estimation of Building Energy Index (BEI) for the cooling load is 655.19 kWh/m²/year.
Meanwhile, the BEI for lighting system is found approximately 150 kWh/m2/year.