Simulation of a simple vapour-compression refrigeration system using R134a
Mohd Yusoff Senawi1, Farah Wahidah Mahmod2.
A computerized simulation of a simple single-stage vapour-compression refrigeration
system has been made. The steady-state simulation uses the accurate property
correlations developed by Cleland for refrigerant R134a. The inputs to the program are:
evaporator pressure, condenser pressure, superheating at evaporator outlet, subcooling at
condenser outlet and compressor isentropic efficiency. The program outputs are:
refrigerating effect, compressor work input, coefficient of performance (COP) and suction
vapour flow rate per kW of refrigeration. An increase in the evaporator pressure from 150 to
250 kPa improves the COP by 40%. The COP is decreased by 35% when the condenser
pressure is increased from 1000 to 1500 kPa. Increasing the superheat at the evaporator
outlet from 0 to 160C improves the COP by 2.6%. An increase in subcooling at the
condenser outlet from 0 to 160C increases the COP by 20%. The COP is improved by 150%
when the compressor isentropic efficiency is increased from 0.4 to 1.